Arc detecting system DC/AC |
 |
The system is based on
experience with arc protection since 1962.
The system units are built into boxes that all fit on a 35 mm
DIN-rail. All front plates are dimensioned to fit the 45 mm slot
in the cover plates of a DIN-system.
The arc detecting relay is connected to light
sensitive detectors suitable placed in the various cubicles or
drawers inside the switchboard. the overcurrent relay is used if
overcurrent as well as an arc has to be present before the
supply circuit breaker is tripped. However, arcing time is
hereby increased.
The time relay is an extra security. It is design to trip a
back-up breaker further back in the supply with a time delay, if
both an arc and an overcurrent are present after tripping of the
supply breaker. |
| Lysbuerelæ DC |
|
 |
601D0100 -
Arc detecting relay 48-220 V
DC for station battery The relay can
monitor up to 16 arc detectors in parallel. In case of an arcing
fault, the relay generates a fast tripping pulse to the circuit
breaker(s) supplying the installation. The delay is less than 1
mSec. The arcing time is thus reduced to the mechanical opening
time of the circuit breaker, reducing personal injury as well as
damage of the installation. The relay is solid state with
complete isolation between input and output. Thus the relay and
the circuit breaker may have different pilot voltages. In
TEST-position the relay can be tested without circuit breaker
tripping. The relay has 2 free signal contacts: One contact is
for remote indication of arcing fault trip. The other contact
indicates absence of pilot voltage - or that the TEST-function
is activated. The sensitivity to light (bias current) is
adjustable within 1-12 mA on the front plate |
 |
601D0500
- Junction box with indication The
unit is designed to connect up to 8 detectors in parallel and
has a separate indication of which detector(s) caused tripping
by means of a red LED for each detector. The red LED is lit when
the light intensity exceeds 6.000 lux. on the detector, but it
turns off again if the intensity goes below 6.000 lux. At 12.000
lux. the arc detecting relay is triggered, the active LED’s are
latched and a yellow LED (TRIP) is turned on. All LED’s remain
turned on until reset by a common RESET button. Max. 2 boxes per
arc detecting relay is allowed. |
 |
601D0400 -
Junction box
For connection of up to 8 detectors in parallel. No
indication. |
 |
601A0200/0300 -
Detector React on light and is
available with 180º or 360º characteristic. To be installed in
each cubicle/drawer and should be shielded from normal switching
arcs. Detectors are supplied with 5 m of cable and a mounting
bracket. |
 |
601D0700 -
Overcurrent relay A 3-phase current
relay to be used in combination with a DC arc detecting relay.
The current setting range is 1.5-3.0xIn (7.5-15A). Each time the
set current is exceeded a red LED (TRIP) turns on and an output
relay activates. The relay contact - normally closed - opens and
cancels the blocking of the arc detecting relay making it able
to trip the supply breaker in the case of an arcing fault. The
function of the arc detecting relay is thus made dependent on
the current at the time of the arcing fault. However arcing time
is increased. |
| Lysbuerelæ AC |
|
 |
601D0900 -
Arc detecting relay AC The relay is
used in combination with junction box 601D0400. (601D0500 cannot
be used). The relay is completely solid state and has complete
isolation between detector input and output. In TEST-mode all
functions of the system can be tested without tripping the
breaker. The relay has energy stored in a storage capacitor
charged with a DC voltage to trip the circuit breaker. The relay
has 2 free signal contacts: One contact is for external
indication of tripping on arcing fault. The other contact
indicates absence of pilot voltage - or that the TEST-function
is activated. Both contacts are activated after tripping as the
relay normally disconnects its own supply voltage. The
sensitivity to light (bias current) is adjustable within 1-12 mA
on the front plate.
|